If you have ever opened a panel schedule or a BS 88 catalogue and found yourself staring at a column of gG and gM designations side by side, you are not alone. The two utilisation categories look similar, carry the same voltage and current ratings, and are physically interchangeable in most fuse-bases — yet specifying the wrong one can cause repeated nuisance tripping on motor circuits or leave cables underprotected.

This guide explains exactly what separates gG from gM, when each is the right choice, and how to apply the relevant IEC 60269 and BS 88 standards when sizing fuses for real-world installations.

What is a utilisation category?

Under IEC 60269-1 and BS 88, every low voltage HRC fuse-link carries a two-letter utilisation category code. The first letter describes the breaking range:

  • g — general purpose, full-range fuse. Can interrupt any current from the minimum fusing current up to the rated breaking capacity.
  • a — back-up fuse. Only interrupts currents above a defined threshold; requires a supplementary device for lower overcurrents.

The second letter describes the application:

  • G — general circuit protection (cables, distribution, mixed loads)
  • M — motor circuit protection

So gG means a full-range general purpose fuse, and gM means a full-range motor protection fuse.

How gG and gM fuses differ

Both gG and gM are full-range fuses compliant with IEC 60269-1. Both protect against overloads and short circuits. The key difference is in their time-current characteristic — the curve that defines how quickly a fuse operates at any given overcurrent multiple.

The gG time-current characteristic

A gG fuse follows a relatively steep time-current curve optimised for cable protection. At two to three times its rated current it operates within a defined time, providing accurate overload protection. This precision is exactly what you want when protecting a distribution cable: you need the fuse to clear a sustained overload before insulation is damaged, but not so slowly that it tolerates excessive heating.

The gM time-current characteristic

A gM fuse has two current ratings: the rated current In (the marking on the fuse body) and the rated motor current Im (the continuous current it is actually designed to carry). In most catalogue entries Im = In, but the fuse’s time-current curve is deliberately shifted to be slower in the overload region compared to a gG of the same marking.

This slower overload response is what allows a gM fuse to survive the inrush current that occurs every time a motor starts. A direct-on-line (DOL) motor can draw five to eight times its full-load amps for several seconds at start-up. A standard gG fuse rated to the motor’s full-load current would see this inrush as an overload and clear — the exact nuisance tripping problem that gM was designed to prevent.

Key insight: gM fuses are not slower overall — they are selectively slower in the overload region to ride through motor inrush, while retaining rapid short-circuit response at high fault currents.

Side-by-side comparison

Property gG gM gG Best For gM Best For
Full name General purpose, full-range Motor circuit, full-range
Breaking range Full range (overload + S/C) Full range (overload + S/C)
Time-current curve Standard gG curve Shifted — slower at overload
Overload tolerance Standard Higher — tolerates motor inrush
Typical application Cable & general circuit protection Motor starters & DOL circuits Distribution boards, cables Motor branch circuits
Standard IEC 60269-1 / BS 88 IEC 60269-1 / BS 88
Cost Lower Slightly higher Budget-sensitive installs Motor-heavy plant

Note: gG and gM fuses are generally interchangeable in the same fuse-base (same size, voltage rating, and BS 88 / IEC 60269 compliance). The difference is in the characteristic, not the form factor.

The motor starting problem in detail

To understand why gM exists, consider a 15 kW DOL motor on a 400 V supply:

  • Full-load current (FLA): approximately 30 A
  • Starting inrush: typically 180–240 A for 2–5 seconds
  • A gG fuse rated at 32 A would see 180 A as roughly 5.6 × In
  • At 5.6 × In, a 32 A gG fuse typically clears in 1–10 seconds depending on the specific characteristic
  • Depending on the motor’s actual start time, a marginal gG fuse can clear during starting — causing nuisance trips on every motor start

The traditional workaround was to oversize the gG fuse — selecting a 50 A or 63 A fuse for a 30 A motor. This stops the tripping but sacrifices overload protection: the fuse no longer provides meaningful protection for the cable feeding the motor starter.

A correctly sized gM fuse eliminates this compromise. Sized to the motor’s FLA, it rides through the inrush without tripping while still protecting the circuit cable against genuine overloads.

 

Sizing gM fuses to BS 88 and IEC 60269

The selection process for gM fuses is straightforward when following the standard:

  • Identify the motor’s full-load current from the nameplate or the motor data sheet.
  • Select a gM fuse with In equal to or slightly above the full-load current. Most manufacturers publish application tables aligning fuse ratings to standard motor sizes.
  • Verify that the fuse’s I²t let-through value is compatible with the cable’s rated withstand. For motor branch circuits, cable sizing must also account for BS 7671 / IEC 60364 requirements.
  • Check coordination with the upstream device. The motor branch circuit gM fuse must coordinate with the main distribution board’s gG fuse so that only the motor branch circuit fuse clears on a fault.

For larger motors, or where the start time is unusually long (e.g. high-inertia loads, variable-speed pump restarts), consult the fuse manufacturer’s application guidance. Lawson Fuses provides detailed time-current characteristic curves and application data for all gM products.

When gG is the right choice

gG remains the correct specification in the majority of general circuit applications:

  • Distribution cable protection in switchgear and distribution boards
  • Transformer primary protection (the brief transformer inrush is handled by gG characteristics)
  • Circuits supplying mixed loads where no single motor dominates
  • Lighting circuits
  • Busbar protection in low voltage switchgear
  • Any application where the load profile does not include significant inrush

gG’s tighter overload characteristic actually makes it more protective in these contexts. Replacing gG with gM on a distribution board main fuse, for example, would reduce overload protection accuracy without offering any benefit.

Quick decision guide

Motor Rating Direct-on-line Start
(3x FLC for 10 sec)
Fuse-Link Rating (Amperes)
Assisted Start
(3.5x FLC for 20 sec)
Fuse-Link Rating (Amperes)
KW HP FLC gG gM gM
0.75 1 2 6 4
1.1 1.5 2.5 10 6
1.5 2 3 10 6
2.2 3 5 16 10
3 4 6.5 20 16
4 5.5 8 25 16
5.5 7.5 11 32 20M25 20
7.5 10 15 40 32M40 25
10 13.5 19 50 32M50 32
12.5 17 21 63 32M63 40
15 20 28 63 32M63 40
18.5 25 35 80 63M80 50
22 30 41 80 63M100 63
25 33 46 100 63M100 63
30 40 55 125 100M160 80
37 50 69 160 100M160 80
45 60 83 200 100M200 100
55 75 100 200 100M200 125
60 80 110 250 200M250 160
75 100 135 250 200M250 160
90 120 160 315 200M315 200
93 125 165 355* 200
110 150 200 400 315M400* 250
132 175 240 400 315M400*
150 200 280* 450* 315M400*
160 215 280 500 400M500* 355*
170 230 300 500 400M500* 355*
185 500 4M500*
200 270 350 630 400
220 300 385 630* 400
250 335 435 710* 500
260 350 450 750* 560
300 400 500 800 630

 

Direct-on-line Start
(3x FLC for 10 sec)
Fuse-Link Rating (Amperes)
Assisted Start
(3.5x FLC for 20 sec)
Fuse-Link Rating (Amperes)
gG gM Maximum
Motor FLC
gG gM Maximum
Motor FLC
2 0.6 2 0.6
4 1.3 4 1.3
6 2 6 2
10 4.1 10 4.1
16 6 16 6
20 7.6 20 7.6
25 20M25 13 25 20M25 13
32 20M32 18 32 20M32 18
40 32M50 26 40 32M50 26
50 32M63 36 50 32M63 36
63 32M63 40 63 32M63 40
80 63M80 40 80 63M80 40
80 65M100 61 80 65M100 61
100 65M100 61 100 65M100 61
125 100M125 82 125 100M125 82
160 100M160 110 160 100M160 110
200 200M250 150 200 200M250 150
200 200M315 170 200 200M315 170
250 315M400* 240 250 315M400* 240
315 315M400* 280 315 315M400* 280
355* 400M500* 310 355* 400M500* 310
450* 400M500* 350 450* 400M500* 350
500 380 500 380
560* 420 560* 420
630* 450 630* 450
670* 460 670* 460
710* 480 710* 480
750 510 750 510
800 510 800 510

 

Assisted Start Maximum
Motor
FLC
(3.5x FLC for 20 sec)
Fuse-Link Rating (Amperes)
“gG” “gM” Maximum
Motor
FLC
2 1.3
4 2
6 3
10 6.4
16 9
20 12
25 20M25 19
32 20M32 24
40 32M40 31
50 32M50 46
63 32M63 51
80 69
100 94
100 110
125 150
160 180
200 210
250 230
315 250
355 310
400M500* 340
450* 400M500* 380
500 430
560* 460
630* 500
670* 530
710* 550
750* 570
800 600

A note on gG/gM marking and interchangeability

Because gG and gM fuses of the same current rating share the same physical dimensions and fuse-base compatibility, it is possible to install one where the other is specified. Do not rely on interchangeability as a shortcut. Installing a gG fuse in a motor circuit that was designed for gM will likely result in nuisance tripping. Installing a gM in a general distribution circuit that was designed for gG will provide slightly less overload protection accuracy.

Always match the utilisation category to the application. When replacing fuses in an existing installation, check the panel schedule or the original design documentation for the specified category before substituting.

Summary

Both gG and gM are full-range HRC fuse-links compliant with IEC 60269 and BS 88. The fundamental difference is in the time-current characteristic:

  • gG: standard overload response — precise, cost-effective, and correct for general circuit and cable protection.
  • gM: extended overload tolerance — designed to ride through motor inrush without nuisance tripping, while retaining full short-circuit protection.

Specify gG as the default for distribution and general circuits. Specify gM for motor branch circuits, sized to the motor’s full-load current. When in doubt, consult the application data in Lawson Fuses’ technical documentation or speak to our technical team.

About Lawson Fuses

Lawson Fuses has specialised in the design, development and manufacturing of low voltage HRC fuse-links and fuse-holders since 1938. Our products comply with IEC 60269 and BS 88 and are ASTA certified and ISO 9001 accredited. For datasheets, Zs values, application guidance, and trade pricing, visit www.lawsonfuses.com or call 01661 823 232.